🔌 NEC Conduit Fill Calculator

Select conduit type and size, then add conductors. NEC Chapter 9, Tables 4 & 5 limits: 53% for 1 wire, 31% for 2 wires, 40% for 3+ wires.

From NEC Chapter 9, Table 4
Conductors
NEC Fill Limits Reference
NEC Chapter 9, Table 1: 1 conductor = 53% max fill · 2 conductors = 31% max fill · 3+ conductors = 40% max fill. These limits apply to all conduit types. Derating for more than 3 current-carrying conductors in a raceway per NEC 310.15(C)(1).
Conduit SizeTypeTotal Area (in²)40% Fill (in²)31% Fill (in²)53% Fill (in²)
THHN/THWN Wire Areas (NEC Ch. 9, Table 5)
AWG / kcmilArea (in²)Diameter (in)Common Use
#140.00970.11115A circuits, control wiring
#120.01330.13020A circuits, general purpose
#100.02110.16430A circuits, HVAC feeders
#80.03660.21640–50A, dryers, small feeders
#60.05070.25455–65A, panel feeders
#40.08240.32470–85A, sub-panel feeders
#30.09730.35285–100A feeders
#20.11580.38495–115A, service entrance
#10.15620.446110–130A, large feeders
#1/00.18550.486125–150A, service entrance
#2/00.22230.532145–175A, main feeders
#3/00.26790.584165–200A, main feeders
#4/00.32370.642195–230A, service entrance
250 kcmil0.39700.711215–255A, large service
300 kcmil0.46080.766240–285A, large service
350 kcmil0.52420.817260–310A, large feeders
400 kcmil0.58630.864280–335A
500 kcmil0.70730.949320–380A, large feeders
600 kcmil0.86591.051355–420A
750 kcmil1.04961.156400–475A, utility primary